Description
Concentrated liquid alkaline product for corrosion and Calcium scale control in boilers. very usefull Concentrated Alkaline Liquid For Maintaining Ph. ( To adjust alkalinity )
Suitable for low-pressure boiler systems (0-32 bar) , medium-pressure steam propulsion vessels (32-60 bar). And also suitable to used for high pressure steam generating systems (60-84 bar).
Mechanism : It converts calcium hardness into soft, non-adherent sludge that is easily removed by blowdown.
Testing control procedure
- Test water sample from the water boiler as described in the direction of the Alkalinity Test Kit ( p & m Total ) http://www.rxmarine.com/Alkalinity-test-kit
- Determine the present alkalinity value expressed as ppm CaCO3 .
- Desired level of 100-150 ppm as CaCO3.
- A control test for the alkalinity of the water should be conducted after 3- 6 hours from the application.
CHARACTERISTICS
- Alkalinity balace mechnism to control corrosion.
- It converts calcium hardness into soft, non-adherent sludge that is easily removed by blowdown. Treated as good salt-scale controler product.
- Compatible with other BOILER chemicals
- Tested with long and continious running plant for more then 20 Years and easy to apply and use.
- Avoid contact with any acidic / oily – FAT materials.