ALKALINITY Titration Method for Boiler & Cooling Water

Lab Testing method not suitable for on site testing, But this method is more accurate and scientifc

SKU: RXSOL-62-5515-002 Category:

Description

ALKALINITY Titration Method for Boiler & Cooling Water ( TITRIMETRIC METHOD 0-200 PPM )

The presence of alkalinity in a water sample may be due to many different substances.  However, for the sake of simplicity, the presence of bicarbonate, carbonate, and hydroxide ions is commonly considered as alkalinity.  The points of change in colour of phenolphthalein and methyl orange indicators, which occur at pH 8.3 and pH 4.3 provide standard reference points which are almost universally used to express alkalinity.

Very high alkalinity values can be undesirable in an industrial water supply.  For example, the presence of a high methyl orange alkalinity should be avoided in boiler feed water because of the resultant carbon dioxide content of the steam.  Carbon dioxide usually is responsible for the corrosion of steam and return lines.  High boiler water alkalinities are also undesirable because the presence of high hydroxide ion concentration is the primary cause of caustic metal embrittlement. A very high boiler alkalinity can also lead to an undesirable carryover condition.  On the other hand, the alkalinity of boiler water must be sufficiently high to protect the boiler metal against acidic corrosion and to ensure precipitation of scale forming salts.  Usual treatment approaches include setting both a minimum alkalinity level and an operating range.
 

Hydroxide alkalinity may be determined by adding barium chloride prior to titration to precipitate the carbonate ion from solution, allowing direct titration of the hydroxide alkalinity.  Measurement of hydroxide alkalinity is also used to control lime soda softeners.

In cooling water systems, alkalinity is of major importance since the total alkalinity of a water is one factor that must be considered when predicting the tendency for the water to precipitate calcium carbonate scale.  Depending on the choice of chemical treatments to protect against corrosion and scale formation, the operating alkalinity and pH ranges are chosen to balance these two features.

Water Testing Procedures Manual ( Full Range Lab testing   Methods with standard  composition ratio Of Reagents  ::: Available with us  at 2700 INR or 54 US$ or 207 AED






top